3 Installation and Commissioning
B17
CP 343-1 Lean for Industrial Ethernet / Manual Part B
Release 09/2009
C79000-G8976-C198-06
3.3 Controlling the operating mode
You have the option of changing the mode of the CP between RUN and STOP
using the STEP 7 / NCM S7 configuration software (PLC > Accessible Nodes).
Procedure
S Switch from STOP to RUN:
The CP reads the configured and/or downloaded data into the work memory
and then changes to the RUN mode.
S Switch from RUN to STOP:
The CP changes to STOP. Established connections (ISO-on-TCP, TCP, UDP
connections) are terminated (transitional phase with LED display “STOPPING”);
The reaction is as follows in STOP:
The communications connections mentioned above are terminated;
The configuration and diagnostics of the CP is possible (system connections
for configuration, diagnostics, and PG channel routing are retained);
HTTP access is possible
The routing function is active
The time of day is not forwarded
PROFINET IO is disabled.