Approvals SCALANCE W700 802.11n
Reference Manual, 01/2017, C79000-G8976-C392-05
44
Approvals for SCALANCE W788C / W786C 802.11n
2.2 General approvals
2.2
General approvals
ATEX (explosion protection directive)
The SIMATIC NET products meet the requirements of the EC directive 94/9/EC "Equipment
and Protective Devices for Use in Potentially Explosive Atmospheres”. and as of 20.04.2016
the EC directive 2014/34/EU.
ATEX classification:
II 3 G Ex nA IIC T4 Gc
KEMA 07ATEX0145 X
The products meet the requirements of the following standards:
EN 60079-15 (electrical apparatus for potentially explosive atmospheres; Type of
protection "n")
EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid ATEX certificates.
WARNING
When using SIMATIC NET products in hazardous area zone 2, make absolutely sure that
the associated conditions in the following document are adhered to:
"SIMATIC NET Product Information Use of subasseblies/modules in a Zone 2 Hazardous
Area".
You will find this document
on the data medium that ships with some devices.
on the Internet pages of Siemens Industry Online Support
(http://support.automation.siemens.com/ww).
Enter the document identification number C234 as the search term.

Other manuals for Siemens SIMATIC NET SCALANCE W700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET SCALANCE W700 and is the answer not in the manual?

Siemens SIMATIC NET SCALANCE W700 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET SCALANCE W700
CategoryWireless Access Point
LanguageEnglish

Related product manuals