4320 Axis %1 function %2 %3 and %4 not allowed
Parameters: %1 = String: Axis identifier
%2 = String: MD identifier
%3 = String: Bit
%4 = String: MD identifier
Definitions: The functions declared by the specified machine data cannot simultaneously be active for one axis.
Reaction: Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Deactivate one of the functions.
Program
Continuation:
Switch control OFF - ON.
4334 Channel %1 The amount of fine correction in parameter %2 of the
orientable toolholder %3 is too large
Parameters: %1 = Channel number
%2 = Invalid parameter of the orientable toolholder
%3 = Number of the orientable toolholder
Definitions: The maximum permissible value of the fine correction in an orientable toolholder is limited by the
machine data $MC_TOCARR_FINE_LIM_LIN for linear variables, and by the machine data
$MC_TOCARR_FINE_LIM_ROT for rotary variables. The alarm can only occur if the setting data
$SC_TOCARR_FINE_CORRECTION is not equal to zero.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
NC Stop on alarm at block end.
Remedy: Enter a valid fine correction value.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
4336 Channel %1 orientable toolholder no. %2 for orientation transformation
%3 does not exist
Parameters: %1 = Channel number
%2 = Number of the orientable toolholder
%3 = Number of the orientation transformation that is to be parameterized with the orientable
toolholder
Definitions: The orientable toolholder, with whose data the orientation transformation is to be parameterized (see
machine data $MC_TRAFO5_TCARR_NO_1/2), does not exist.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
NC Stop on alarm at block end.
Remedy: Enter a valid tool-carrier number.
Program
Continuation:
Clear alarm with the RESET key. Restart part program