02.00 Function diagrams
SIEMENS AG 6RX1700-0AD76 8-15
SIMOREG DC Master Operating Instructions
Sheet G126 Motorized potentiometer
y
y = 0
y = x
dy/dt
x
1
1
0
1
0
0
1
0
10
60 1
87564321
-1
*
P465.F(0)
(0...1)
1
1 0
0 0
1 1
0 1
- G126 -
1
0
-1
*
P462.F(10,00s)
(0,01...300,00s)
P461.F (0)
K
P465.F(0)
(0...1)
K0241
K0240
K0242
P467.F(0,0)
(-199,9...+199,9%)
P468.F(+100,00%)
(-199,99...+199,99%)
P469.F(-100,00%)
(-199,99...+199,99%)
P463.F(10,00s)
(0,01...300,00s)
P464.F(10,00s)
(0,01...300,00s)
B0241
P472.B (0)
B
P471.B (0)
B
P470.B (0)
B
B0240
P466.F (0)
K
P473.F (0)
P460.F (1)
Bit14
Bit13
Motorized potentiometer
Acceleration time
Output = 0
(Capacitor symbolizes
value memory)
Automatik setpoint
Clockwise
/Counterclockwise
Manual/Automatic
Set motorized
potentiometer
Setting value
Setpoint from
motorized potentiometer
MOP Starting value
MOP max.MOP min.
0 ... The motorized potentiometer ramp-function generator is bypassed in
automatic mode (effect as for P462 and P463 = 0)
1 ... The motorized potentiometer ramp-function generator is effective in
the manual and automatic modes
0 ...
No storage of output value :
K240 is set to 0 in all operating states of > o5
The starting point after ON is specified by P467 (MOP starting value)
1 ...
Non-volatile storage of output value :
K240 remains stored in all operating states
Decelerartion time
Time difference
Increase motorized potentiometer
from control word 1
Decrease motorized potentiometer
from control word1
Ramp-function generator
with permanent memory
Acceleration/deceleration
completed
Motorized potentiometer operating mode