Function descriptions 02.00
9-2 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Binectors
All binary output quantities and important binary output signals of the function blocks are available as
"Binectors" (connectors
for binary signals). Binectors can assume states log. "0" and log."1". The
quantities accessed via binectors correspond to output signals or measuring points in a digital circuit
and are identified by their "Binector number" (e. g. B0003 = binector 3).
Special cases: B0000 = Fixed value log."0"
B0001 = Fixed value log."1"
A list of available binectors can be found in Section 12.
Example: The status of terminal 36 is available at B0010 and, in inverted form, at binector B0011
(Section 8, Sheet G110)
1
24V
5V
36
M
B0011
B0010
Selection switches, connections
(see also Section "Data sets")
The inputs of function blocks are defined at "selection switches"
by setting the appropriate selection
parameters. The input is defined by entering the number of the connector or binector to be applied as
the input quantity in the parameter for the relevant selection switch.
Representation in function diagrams (examples):
P750 (0)
K
Selection of a connector
Parameter number = P750, factory setting = 0 (i. e. fixed value 0%)
P704 (0)
B
Selection of a binector
Parameter number = P704, factory setting = 0 (i. e. fixed value 0)
.01
.02
.03
.04
P613 (1)
K
K
K
K
Selection of connectors ("indexed" parameter with 4 indices)
Parameter number = P613, factor setting = 1 (i. e. fixed value 100%; this factory
setting applies to all the indices of P613)
P611
K
K
K
K
.01
.02
.03
.04
277
WE
0
0
0
Selection of connectors ("indexed" parameter with 4 indices)
Parameter number = P611
Factory setting for index .01 = 277 (i. e. connection with connector K0277)
Factory setting for indices .02 to .04 = 0 (i. e. fixed value 0%)
P046 (0)
B
B
B
B
.01
.02
.03
.04
Selection of binectors ("indexed" parameter with 4 indices)
Parameter number = P046, factory setting = 0 (i. e. fixed value 0, this factory setting
applies to all the indices of P046)
The selected setting can be entered in the empty field (fields). The value in brackets next to the
parameter number is the factory setting of the selection parameter.