EasyManua.ls Logo

Siemens SIMOREG DC Master 6RA7018-6DS22 - Page 375

Siemens SIMOREG DC Master 6RA7018-6DS22
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
02.00 Faults / Alarms
SIEMENS AG 6RX1700-0AD76 10-11
SIMOREG DC Master Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
F042 Tachometer fault
(active in operating states of – –, I, II)
A check is performed every 20ms to ensure that
(K0287) EMF Actual
(K0179) speedActual
is > +5%
If the check result is incorrect for 4 times in succession, the fault message is activated.
The following rule applies:
100% actual speed = maximum speed
100% actual EMF = ideal average DC voltage at
α 0, i.e. when the thyristor bridge is fully gated
The ideal DC voltage average value at
α = 0 is
23
P078.001
The monitoring function is effective only if the EMF > a % of
23
P078.001
"a" is a percentage that can be set in parameter P357 (default setting 10%).
The monitoring function is effective only if the armature current is > 2% of the converter rated DC current set in r072.002.
Possible fault causes
Open circuit in tachometer or pulse encoder cable.
Tachometer of pulse encoder cable incorrectly connected.
Pulse encoder supply has failed.
Polarity for actual speed value (P743) is incorrectly set.
Armature circuit data (P110 und P111) are incorrectly set (execute current controller optimization run).
Tachometer or pulse encoder defective
Pulse encoder supply voltage is incorrectly set (P140)
The field polarity is not reversed by the external hardware when the field is reversed.
Fault value: r047 Index 002 to 016:
1 Open circuit in tachometer or pulse encoder cable i002 Actual speed value (K0179) in case of fault
2 Polarity of tachometer or pulse encoder is incorrect i003 Actual EMF value (K0287) in case of fault
F043 EMF too high for braking operation
(active in operating states of – –, I, II)
This fault message is activated if the following 5 conditions are fulfilled when a torque direction reversal is requested (selection
of MI or MII):
P272=0 (fault message is parameterized and not alarm + field weakening)
A parameterized, additional, torque-free interval (P160 0) has expired
Parallel drive is ready for engagement of the new torque direction
The absolute value of the armature current (K0118) requested in the new torque direction is >0.5% of P072
The calculated firing angle (K0101) for the armature current requested for the new torque direction is >165 degrees.
Possible fault causes
No “speed-dependent field weakening" (P081=0) is parameterized even though operation in the field weakening range is
needed for the requested maximum speed
Note:
In motor operation, it is possible to reach EMF values corresponding to the peak of the phase-to-phase supply voltage at a
firing angle of α
G
=30° (rectifier stability limit P150) and low armature currents.
Setpoint EMF for field weakening operation too high (parameter P101 is set too high)
Supply voltage dip
EMF controller or field current controller is not optimized, possibly resulting in excessive EMF on power-up.
Fault value: r047 Index 002 to 016:
Calculated firing angle (armature) before limitation (K0101) i002 Instantaneously measured actual EMF (K0287)
i003 Armature current controller setpoint (K0118)
F044 A slave connected to the paralleling interface is not operating
(active when U800 = 1 or 2 and U806>10 (master) after receipt of the first valid protocol in operating states – –, I, II)
Fault value:
1 A fault message is active on a slave
2 A slave is not in operation (e.g. because its enable input is set to "0")

Table of Contents

Related product manuals