02.00 Faults / Alarms
SIEMENS AG 6RX1700-0AD76 10-27
SIMOREG DC Master Operating Instructions
Alarm
No.
Description
A081 CB alarm from 1
st
CB
(active in operating states ≤ o11)
For PROFIBUS board (CB1 or CBP):
The combinations of identifier bytes sent in the configuration message by the DP Master do not conform to the permitted
identifier byte combinations (configuring error in DP Master)
Effect: No link is set up with the DP Master; re-configuration necessary.
A082 CB alarm from 1
st
CB
(active in operating states ≤ o11)
For PROFIBUS board (CB1 or CBP):
No valid PPO type can be identified from the configuration message sent by the DP Master.
Effect: No link is set up with the DP Master; re-configuration necessary.
A083 CB alarm from 1
st
CB
(active in operating states ≤ o11)
For PROFIBUS board (CB1 or CBP):
No useful data or invalid useful data have been received from the DP Master.
Effect: The process data are not transferred to the basic unit. When the message timeout monitor is active (U722 set to value
other than 0), fault message F082 with fault value 10 is output.
A084 CB alarm from 1
st
CB
(active in operating states ≤ o11)
For PROFIBUS board (CB1 or CBP):
The data exchange between the communications board and DP Master has been interrupted.
Effect: When the message timeout monitor is active (U722 set to value other than 0), fault message F082 with fault value 10 is
output.
A085 CB alarm from 1
st
CB
(active in operating states ≤ o11)
For PROFIBUS board (CB1 or CBP):
Error in DPS software of communications board.
Effect: Fault message F081 is output.
A086
to
A088
CB alarm from 1
st
CB
(active in operating states ≤ o11)
A089 CB alarm from 2
nd
CB
(active in operating states ≤ o11)
Meaning as for A081, but from 2
nd
CB.
A090 CB alarm from 2
nd
CB
(active in operating states ≤ o11)
Meaning as for A082, but from 2
nd
CB.
A091 CB alarm from 2
nd
CB
(active in operating states ≤ o11)
Meaning as for A083, but from 2
nd
CB.
A092 CB alarm from 2
nd
CB
(active in operating states ≤ o11)
Meaning as for A084, but from 2
nd
CB.
A093 CB alarm from 2nd CB
(active in operating states ≤ o11)
Meaning as for A085, but from 2
nd
CB.
A094
to
A096
CB alarm from 2nd CB
(active in operating states ≤ o11)
A097
to
A128
TB alarms
(active in operating states ≤ o11)
For more information about TECH BOARD alarms, please refer to Operating Instructions or Configuring Guide of the relevant
board.