02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-13
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
r064 Board compatibility
Compatibility identifier of boards in locations 1 to 3 of electronics box.
The compatibility identifier is bit-coded. To ensure the compatibility of a
board, it must have a "1" setting at the same bit location of the parameter
value as the CUD (in location 1 / index i001).
Indices:
i001: Compatibility identifier of board in location 1
i002: Compatibility identifier of board in slot D
i003: Compatibility identifier of board in slot E
i004: Compatibility identifier of board in slot F
i005: Compatibility identifier of board in slot G
Example:
Index Value Bit representation Compatible with CUD
i001 253 0000 0000 1111 1101
i002 002 0000 0000 0000 0010 no
i003 001 0000 0000 0000 0001 yes
Ind: 5
Type: O2
P052 = 3
r065 Software identifiers
Extended software version identifiers in locations 1, 2, and 3 of the
electronics box
Indices:
i001: Software identifier of the board in location 1
i002: Software identifier of the board in slot D
i003: Software identifier of the board in slot E
i004: Software identifier of the board in slot F
i005: Software identifier of the board in slot G
Ind: 5
Type: O2
P052 = 3
11.5 Definition of SIMOREG DC MASTER power section
P067
*
Load class [SW1.8 and later]
1 Load class DC I
2 Load class DC II
3 Load class DC III
4 Load class DC IV
5 US rating
The load classes are described in Chapter 3.4.1.
Depending on the load class selected, the device rated DC of the
SIMOREG DC Master is reduced to a value of different magnitude to suit
the power section and load class.
The current value of the device rated DC is indicated in parameter
r072.002.
Note:
If the device rated DC is reduced via parameter P076.001, the lesser of the
two values is active.
1 to 5
1
Ind: None
FS=1
Type: O2
P052 = 3
P051 = 40
off-line
r068 Options according to rating plate
0 No option
1 Option L04 (low voltage, 85V)
2 Option K01 (terminal expansion)
3 L04 and K01
Ind: None
Type: 02
P052 = 3
r069 Serial number of SIMOREG DC Master converter
i001: 1
st
and 2
nd
places of serial number
i002: 3
rd
and 4
th
places of serial number
i003: 5
th
and 6
th
places of serial number
i004: 7
th
and 8
th
places of serial number
i005: 9
th
and 10
th
places of serial number
i006: 11
th
and 12
th
places of serial number
i007: 13
th
and 14
th
places of serial number
i008 to i015: 0
i016: Checksum for serial number
The serial number ASCII code is displayed in this parameter. The number
is output in plaintext on the OP1S panel.
Ind: 16
Type: L2
P052 = 3