02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-19
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P101
*
FDS
Rated motor armature voltage (acc. to motor rating plate)
Notes:
One of the functions of this parameter is to determine the point at which
field-weakening operation commences.
If possible, the rated motor armature voltage + the voltage drop in the motor
feeder cable (for a current setting acc. to P100) should be set in P101.
10 to 1000
[V]
1V
Ind: 4
FS=400
Type: O2
P052 = 3
P051 = 40
Offline
P102
*
FDS
Rated motor field current (acc. to motor rating plate)
0.00 Parameter not yet set
0.00 to 100.00
[A]
0.01A
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P103
*
FDS
Minimum motor field current
Note:
P103 must be set to <50% of P102 to execute the optimization run for field
weakening (P051=27).
0.00 to 100.00
[A]
0.01A
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Offline
P104
*
FDS
Speed n1 (acc. to motor rating plate)
1
st
point (speed value) in speed-dependent current limitation.
This parameter is used together with P105, P106, P107 and P108 to define
the characteristic of the current limiting value as a function of actual speed.
1 to 10000
[rev/min]
1rev/min
Ind: 4
FS=5000
Type: O2
P052 = 3
P051 = 40
Offline
P105
*
FDS
Armature current I1 (acc. to motor rating plate)
1
st
point (current value) in speed-dependent current limitation.
This parameter is used together with P104, P106, P107 and P108 to define
the characteristic of the current limiting value as a function of actual speed.
0.1 to 6553.0
[A]
0.1A
Ind: 4
FS=0.1
Type: O2
P052 = 3
P051 = 40
Offline
P106
*
FDS
Speed n2 (acc. to motor rating plate)
2
nd
point (speed value) in speed-dependent current limitation.
This parameter is used together with P104, P105, P107 and P108 to define
the characteristic of the current limiting value as a function of actual speed.
1 to 10000
[rev/min]
1rev/min
Ind: 4
FS=5000
Type: O2
P052 = 3
P051 = 40
Offline
P107
*
FDS
Armature current I2 (acc. to motor rating plate)
2
nd
point (current value) in speed-dependent current limitation.
This parameter is used together with P104, P105, P106 and P108 to define
the characteristic of the current limiting value as a function of actual speed.
0.1 to 6553.0
[A]
0.1A
Ind: 4
FS=0.1
Type: O2
P052 = 3
P051 = 40
Offline
P108
*
FDS
Maximum operating speed n3
When the speed-dependent current limitation is in use, the maximum speed
which is defined by the selection of the actual speed source as set in P083,
must be entered in this parameter:
When P083=1 (analog tacho):
Speed at which a tacho voltage as set in P741 is reached
When P083=2 (pulse encoder):
Same value as maximum speed set in P143
When P083=3 (operation without tacho):
Speed at which EMF as set in P115 is reached
1 to 10000
[rev/min]
1rev/min
Ind: 4
FS=5000
Type: O2
P052 = 3
P051 = 40
Offline
P109
*
FDS
Control word for speed-dependent current limitation
0 Speed-dependent current limitation is deactivated
1 Speed-dependent current limitation is activated
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P110
FDS
Armature circuit resistance
This parameter is set automatically during the optimization run for
precontrol and current controller (armature and field) (P051=25).
0.000 to 32.767
[Ω]
0.001Ω
Ind: 4
FS=0.000
Type: O2
P052 = 3
P051 = 40
Online
P111
FDS
Armature circuit inductance
This parameter is set automatically during the optimization run for
precontrol and current controller (armature and field) (P051=25).
0.000 to 327.67
[mH]
0.01mH
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P112
FDS
Field circuit resistance
This parameter is set automatically during the optimization run for
precontrol and current controller (armature and field) (P051=25).
0.0 to 3276.7
[Ω]
0.1Ω
Ind: 4
FS=0.0
Type: O2
P052 = 3
P051 = 40
Online
P114
FDS
Thermal time constant of motor
(see Section 9.15)
0.0 I
2
t monitoring deactivated
0.0 to 80.0
[min]
0.1min
Ind: 4
FS=10.0
Type: O2
P052 = 3
P051 = 40
Online
P115
FDS
EMF at maximum speed in operation without tachometer
This parameter is used to adjust the speed in cases where the internal
actual EMF value is applied as the actual speed value. P115 defines the
EMF which corresponds to maximum speed as a percentage of P078.001.
1.00 to 140.00
[% of P078.001]
0.01%
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online