02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-33
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.14 Ramp-function generator
(see also Section 8, Sheet G136 and Section 9)
See P639 and P640 for ramp-function generator setting parameters
Limitation at ramp-function generator output (setpoint limiting))
The effective limitations are:
Upper limit: Minimum value of P300 and the four connectors selected with P632
Lower limit: Maximum value of P301 and the four connectors selected with P633
Note: The limiting values for both the positive and negative setpoint limits can have a positive or negative sign. The negative setpoint
limit, for example, can therefore be parameterized to a positive value and the positive setpoint limit to a negative value.
P300
FDS
Positive limitation at ramp-function generator output
-200.00 to 199.99
[%]
0.01%
Ind: 4
FS=100.00
Type: I2
P052 = 3
P051 = 40
Online
P301
FDS
Negative limitation at ramp-function generator output
-200.00 to 199.99
[%]
0.01%
Ind: 4
FS=-100.00
Type: I2
P052 = 3
P051 = 40
Online
P302
*
FDS
Select ramp-function generator / ramp-up integrator mode
0 Normal ramp-function generator operation
Ramp-function generator setting 1 (P303 to P306) is applied.
When a binary selectable input parameterized as "Ramp-
function generator setting 2" (P307 to P310)” (selected in P637)
or ”Ramp-function generator setting 3" (P311 to P314)”
(selected in P638), generator setting 2 or 3 is applied as
appropriate.
1 Ramp-up integrator operation: When the setpoint is reached for
the first time, ramp-function generator setting 1 is switched over
to a ramp-up/down times = 0
2 Ramp-up integrator operation: When the setpoint is reached for
the first time, ramp-function generator setting 1 is switched over
to generator setting 2 (P307 to P310)
3 Ramp-up integrator operation: When the setpoint is reached for
the first time, ramp-function generator setting 1 is switched over
to generator setting 3 (P311 to P314)
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Ramp-function generator parameter set 1
P303
FDS
Ramp-up time 1
0.00 to 650.00
[s]
0.01s
Ind: 4
FS=10.00
Type: O2
P052 = 3
P051 = 40
Online
P304
FDS
Ramp-down time 1
0.00 to 650.00
[s]
0.01s
Ind: 4
FS=10.00
Type: O2
P052 = 3
P051 = 40
Online
P305
FDS
Lower transition rounding 1
0.00 to 100.00
[s]
0.01s
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P306
FDS
Upper transition rounding 1
0.00 to 100.00
[s]
0.01s
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Ramp-function generator parameter set 2
Ramp-function generator parameter set 2 is selected via the binector parameterized in P637.
P307
FDS
Ramp-up time 2
0.00 to 650.00
[s]
0.01s
Ind: 4
FS=10.00
Type: O2
P052 = 3
P051 = 40
Online
P308
FDS
Ramp-down time 2
0.00 to 650.00
[s]
0.01s
Ind: 4
FS=10.00
Type: O2
P052 = 3
P051 = 40
Online
P309
FDS
Lower transition rounding 2
0.00 to 100.00
[s]
0.01s
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P310
FDS
Upper transition rounding 2
0.00 to 100.00
[s]
0.01s
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online