02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-37
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Setpoint/actual value deviation
P388
FDS
Permissible deviation between setpoint and actual value
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
P389
FDS
Hysteresis for setpoint/actual value deviation signal
This value is added to the response threshold if a setpoint/actual value
deviation signal is active
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
P390
FDS
Response delay for setpoint/actual value deviation signal
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=3.0
Type: O2
P052 = 3
P051 = 40
Online
I
f
< I
f min
signal
P394
FDS
Field current threshold I
f min
Field current threshold for I
f
< I
f min
limit-value monitor
.
Note:
This threshold affects the sequence of control operations for the "Direction
of rotation reversal using field reversal" and "Braking with field reversal"
functions (see Section 9).
The I
f
< I
f min
signal is connected to binector B0215, the actual value at
field current controller input K0265 is applied as I
f
.
B0215 = 0 when K0265 > threshold set in P394
B0215 = 1 when K0265 < threshold set in P394 + hysteresis set in P395
0 1 transition takes place when K0265 < P394
1 0 transition takes place when K0265 > P394 + P395
0.00 to 199.99
[%]
0.01% of converter
rated field DC
current (r073.i02)
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
P395
FDS
Hysteresis for I
f
< I
f min
signal
This value is added to the response threshold if I
f
< I
f min
is active.
(see also P394)
0.00 to 100.00
[%]
0.01% of converter
rated field DC
current (r073.i02)
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
I
f
< I
f x
signal
P398
FDS
Field current threshold I
f x
Setpoint-oriented field current threshold for I
f
< I
f x
limit-value monitor.
Note:
This threshold affects the sequence of control operations for the "Direction
of rotation reversal using field reversal" and "Braking with field reversal"
functions (see Section 9).
The I
f
< I
f x
signal is connected to binector B0216, the actual value at field
current controller input K0265 is applied as I
f
.
B0216 = 0 when K0265 > threshold set in P398
B0216 = 1 when K0265 < threshold set in P398 + hysteresis set in P399
0 1 transition takes place when K0265 < P398
1 0 transition takes place when K0265 > P398 + P399
0.00 to 199.99
[%]
0.01% of setpoint at
field current
controller input
(K0268)
Ind: 4
FS=80.00
Type: O2
P052 = 3
P051 = 40
Online
P399
FDS
Hysteresis for I
f
< I
f x
signal
This value is added to the response threshold if I
f
< I
f x
is active.
(see also P398)
0.00 to 100.00
[%]
0.01% of converter
rated field DC
current (r073.i02)
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
11.18 Settable fixed values
Function: The value set in the parameter is applied to the specified connector
P401
FDS
K401 fixed value
is applied to connector K0401
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P402
FDS
K402 fixed value
is applied to connector K0402
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P403
FDS
K403 fixed value
is applied to connector K0403
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online