Parameter list 02.00
11-60 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P685
*
BDS
Source for control word 2, bit25
(0=n controller disabled, 1=n controller enabled)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P686
*
BDS
Source for control word 2, bit26
(0=external fault 2, 1=no external fault 2)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P687
*
BDS
Source for control word 2, bit27
(0=master drive, speed control, 1=slave drive, torque control)
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P688
*
BDS
Source for control word 2, bit28
(0=external alarm 1, 1=no external alarm 1)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P689
*
BDS
Source for control word 2, bit29
(0=external alarm 2, 1=no external alarm 2)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P690
*
Source for control word 2, bit30
(0=select Bico data set 1, 1=select Bico data set 2)
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P691
*
BDS
Source for control word 2, bit31
(main contactor checkback signal)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
11.34 Further configuring measures
P692
*
BDS
Source for selection of injection of standstill field
Selection of binector to control injection of the standstill field ("0" state =
inject standstill field)
Note: The delay time set in P258 is not effective when this function is
active.
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P693
*
BDS
Source for selection of enabling command for EMF controller
Selection of binector which is to control enabling of the EMF controller
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P694
*
BDS
Source for selection of enabling command for "Torque limit
switchover”
Selection of binector which is to control enabling of the "Torque limit
switchover" function (1=enable, see also Sheet G160 in Section 8 and
P180 to P183)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P695
*
BDS
Source for selection of "Set speed controller I component" function
Selection of binector to control the "Set I component" function
0 = binector B0000
1 = binector B0001
etc.
When the binector selected in P695 switches from log. "0" to log. "1", the I
component of the speed controller is set to the value of the connector
selected in P631.
With this function it is possible, for example, to use the same signal
(binector) to control controller enabling commands and setting of the I
component.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline