02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-103
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U277
(2277)
S00
Filter time FB 104
0 to 1000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
DT1 element 3 (output = K9227, inverted: K9228)
U278
(2278)
*
S00
Source for input quantity FB 105
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U279
(2279)
S00
Derivative-action time FB 105
0 to 1000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
U280
(2280)
S00
Filter time FB 105
0 to 1000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
Characteristic blocks
The curve of the characteristics can be defined by 10 points each:
Index i001 to i010 of the parameters for the x values (U282, U285, U288): x values for FB 106, FB 107, FB 108
Index i001 to i010 of the parameters for the y values (U283, U286, U289):associated y values
SW1.8 and later:
Index i011 to i020 of the parameters for the x values (U282, U285, U288):x values for FB 280, FB 282, FB 284
Index i011 to i020 of the parameters for the y values (U283, U286, U289):associated y values
Index i021 to i030 of the parameters for the x values (U282, U285, U288):x values for FB 281, FB 283, FB 285
Index i021 to i030 of the parameters for the y values (U283, U286, U289):associated y values
for x = -200.00% up to x value acc. to index i001 (or i011 or i021) of the parameter for the x values gilt:
y = value acc. to index i001 (or i011 or i021) of the parameter for the y values
for x = x value acc. to index i010 (or i020 or i030) of the parameter for the x values to x = 200.00% gilt:
y = value acc. to index i010 (or i020 or i030) of the parameter for the y values
The distance between two adjacent x or y values must not be more than 199.99% otherwise deviations from the required shape of the
characteristic can arise.
Characteristic block 1 (output = K9229) FB 106
Characteristic block 4 (output = K9410) [SW1.8 and later] FB 280
Characteristic block 5 (output = K9411) [SW1.8 and later] FB 281
U281
(2281)
*
S00
Source for input quantity
0 = Connector K0000
1 = Connector K0001
etc.
Up to SW 1.7:
Selected connector = input quantity for FB106
SW 1.8 and later:
i001 Input quantity for FB106
i002 Input quantity for FB280
i003 Input quantity for FB281
All connector
numbers
1
Ind:
None
[up to SW
1.7]
3
[SW 1.8 and
later]
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U282
(2282)
S00
x values
i001 1st characteristic point for FB106
i002 2nd characteristic point for FB106
...
i010 10th characteristic point for FB106
SW 1.8 and later:
i011 1st characteristic point for FB280
i012 2nd characteristic point for FB280
...
i020 10th characteristic point for FB280
i021 1st characteristic point for FB281
i022 2nd characteristic point for FB281
...
i030 10th characteristic point for FB281
-200.00 to 199.99
[%]
0.01
Ind:
10
[up to SW
1.7]
30
[SW 1.8 and
later]
FS=0.00