02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-115
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
D flipflops
D flipflops with RESET (Q=0), SET (Q=1) and STORE (Q=D on transition from 0 to 1) (priority: 1
st
RESET, 2
nd
SET, 3
rd
STORE).
RESET setting is enabled on POWER ON.
U430
(2430)
*
S00
Source for SET, D, STORE and RESET for D flipflop 1 FB 230
(outputs: Q = B9490, /Q = B9491)
i001 Source for SET
i002 Source for D
i003 Source for STORE
i004 Source for RESET
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U431
(2431)
*
S00
Source for SET, D, STORE and RESET for D flipflop 2 FB 231
(outputs: Q = B9492, /Q = B9493)
As for U430
All binector numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U432
(2432)
*
S00
Source for SET, D, STORE and RESET for D flipflop 3 FB 232
(outputs: Q = B9494, /Q = B9495)
As for U430
All binector numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U433
(2433)
*
S00
Source for SET, D, STORE and RESET for D flipflop 4 FB 233
(outputs: Q = B9496, /Q = B9497)
As for U430
All binector numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
Timer 1 (0.000 to 60.000s) (output = B9580, inverted: B9581)
U440
(2440)
*
S00
Source for input signal and reset signal for timer element 1 FB 240
i001 Source for input signal
i002 Source for reset signal for the pulse generator (if U442=3)
(in state "1", the pulse generator is set to "0")
Settings:
0 = Binector B0000
1 = Binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U441
(2441)
S00
Time for timer 1 FB 240
0.000 to 60.000
[s]
0.001
Ind: None
FS=0.000
Type: O2
P052 = 3
P051 = 40
Offline
U442
(2442)
*
S00
Mode for timer 1 FB 240
0 ON delay
1 OFF delay
2 ON / OFF delay
3 Pulse generator with positive edge triggering
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Timer 2 (0.000 to 60.000s) (output = B9582, inverted: B9583)
U443
(2443)
*
S00
Source for input signal and reset signal for timer element 2 FB 241
As for U440
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U444
(2444)
S00
Time for timer 2 FB 241
0.000 to 60.000
[s]
0.001
Ind: None
FS=0.000
Type: O2
P052 = 3
P051 = 40
Offline
U445
(2445)
*
S00
Mode for timer 2 FB 241
As for U442
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Timer 3 (0.000 to 60.000s) (output = B9584, inverted: B9585)
U446
(2446)
*
S00
Source for input signal and reset signal for timer element 3 FB 242
As for U440
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline

Table of Contents