Parameter list 02.00
11-118 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.62 Technology controller
Parameters apply only if optional S00 technology software is installed
Technology controller: Actual value
U480
(2480)
*
S00
Source for actual value FB 114
Selection of connectors to be added as the actual value
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U481
(2481)
S00
FDS
Filter time for actual value FB 114
0.00 to 600.00
[s]
0.01
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U482
(2482)
S00
FDS
Derivative-action time for actual value (D component) FB 114
0.000 = D component deactivated
See also U483
0.000 to 30.000
[s]
0.001
Ind: 4
FS=0.000
Type: O2
P052 = 3
P051 = 40
Online
U483
(2483)
*
S00
FDS
Factor for derivative-action time FB 114
0 Derivative-action time = U482 * 1
1 Derivative-action time = U482 * 1000
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Technology controller: Setpoint
U484
(2484)
*
S00
Source for setpoint FB 114
Selection of connectors to be added as the setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U485
(2485)
S00
FDS
Injectable additional setpoint FB 114
This parameter setting is added to the setpoint when the binector selected
in U486 changes to the log. "1" state
-200.00 to 199.99
[%]
0.01
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
U486
(2486)
*
S00
Source for control bit for injection of additional setpoint FB 114
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U487
(2487)
S00
FDS
Filter time for setpoint FB 114
0.00 to 600.00
[s]
0.01
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Technology controller: Controller parameters
U488
(2488)
S00
FDS
P gain FB 114
0.10 to 200.00
0.01
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
U489
(2489)
*
S00
Source for input quantity (x) for Kp adaptation FB 114
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U490
(2490)
S00
FDS
Characteristic for Kp adaptation: Threshold 1 (x1) FB 114
0.00 to 200.00
[%]
0.01
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U491
(2491)
S00
FDS
Characteristic for Kp adaptation: Threshold 2 (x2) FB 114
0.00 to 200.00
[%]
0.01
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online