Parameter list 02.00
11-34 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Ramp-function generator parameter set 3
Ramp-function generator parameter set 3 is selected via the binector parameterized in P638.
P311
FDS
Ramp-up time 3
0.00 to 650.00
[s]
0.01s
Ind: 4
FS=10.00
Type: O2
P052 = 3
P051 = 40
Online
P312
FDS
Ramp-down time 3
0.00 to 650.00
[s]
0.01s
Ind: 4
FS=10.00
Type: O2
P052 = 3
P051 = 40
Online
P313
FDS
Lower transition rounding 3
0.00 to 100.00
[s]
0.01s
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P314
FDS
Upper transition rounding 3
0.00 to 100.00
[s]
0.01s
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Displays
r315 Display of effective times
i001: Display of effective ramp-up time
i002: Display of effective ramp-down time
i003: Display of effective lower transition rounding
i004: Display of effective upper transition rounding
0.00 to
650.00 / 10.00
[s]
0.01s
Ind: 4
Type: O2
P052 = 3
r316 Display of ramp-function generator status
Mode of representation on operator panel (PMU):
32104567
15
Segment:
0 RFG enable
1RFG start
2 Setpoint enable & /OFF1
3Set RFG
4 RFG tracking
5 Bypass RFG
7 Ramp-down
15 Ramp-up
Ind: None
Type: V2
P052 = 3
P317
*
FDS
Ramp-function generator tracking
0 Ramp-function generator tracking is not active
1 Ramp-function generator tracking is active
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P318
*
FDS
Set ramp-function generator output
This parameter determines how the ramp-function generator output is set at
the commencement of a "Shutdown" process:
0 The ramp-function generator output is not set at the
commencement of a "Shutdown" process”
1 At the commencement of "Shutdown", the output is set to the
actual speed value K0167 (actual speed value K0167 is
"unfiltered")
2 At the commencement of "Shutdown", the output is set to the
actual speed value K0179 (value is filtered by PT1 in P200,
other filters may also be active)
(setting may not be used in conjunction with P205 > 0)
During a "Shutdown" process, the limitation at the ramp-function generator
output is not effective. P318 must be set to 1 or 2 to prevent any
(temporary) excess speed during "Shutdown" when the generator output is
limited.
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P319
FDS
Delay time for enabling ramp-function generator [SW 1.5 and later]
0,00 to 10,00
[s]
0,01s
Ind: 4
FS=0,05
Type: O2
P052 = 3
P051 = 40
Online