Connections 02.00
6-62 Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Options:
Terminal expansion CUD2 (C98043-A7006)
Terminal type:
Plug-in terminal (screw-type)
Max. connection cross-section 1.5mm
2
Motor interface (see also function diagrams, Section 8, sheets G185 and G186)
Function Terminal
X164
Connection values/Remarks
Motor temp. positive terminal
Motor temp. negative terminal
204
205
Sensor acc. to P490 index 2
Terminal
X161
Supply binary inputs
(output)
210 24V DC, internal short-circuit-proof supply referred to
internal ground.
The sum of the currents drawn from terminals 34, 44
and 210 must not exceed 200 mA.
Overload response: Fault message F018
Binary input
Binary input
Binary input
Binary input
211
212
213
214
H signal:+13V to +33V
L signal:– 33V to +3V or terminal open
Input resistance = 2.8kΩ
Ground for binary inputs
Ground for binary inputs
M
215
216
217
can be isolated from internal ground
(open wire jumper between terminals
216 and 217)
Analog inputs (see also Section 8, sheet G114)
Function Terminal
X164
Connection values/Remarks
Select input analog 2
Ground analog
8
9
Select input analog 3
Ground analog
10
11
±10V, 52kΩ
Resolution: ±10bit
Common mode suppression: ±15V
Analog outputs (see also Section 8, sheet G116)
Function Terminal
X164
Connection values/Remarks
Select output analog 3
Ground analog M
18
19
Select output analog 4
Ground analog M
20
21
0. . . ±10V, max. 2mA
Short-circuit-proof
Resolution ±11bit