Commissioning
7.3 Switching on
1MB..1/2/3/4 - shaft heights 63 ... 355
96 Operating Instructions, 06/2020, A5E44455710A
5. In case of uneven running or abnormal noise, switch off the machine. As the machine
runs down, identify the cause.
If the mechanical operation improves immediately after the machine is switched off,
then the cause is magnetic or electrical.
If the mechanical running does not improve immediately after switching the machine
off, then the cause is mechanical.
- Imbalance of the electrical machine or the driven machine
- The machine set has not been adequately aligned
- The machine is being operated at the system resonance point. System = motor, base
frame, foundation, ...
NOTICE
Serious damage to the machine
If the vibration values in operation are not maintained in accordance with DIN ISO
10816-3, then the machine can be mechanically destroyed.
During operation, observe the vibration values in accordance with
DIN ISO 10816-3.