EasyManua.ls Logo

Siemens SIMOTION D445-2

Siemens SIMOTION D445-2
394 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning (software)
6.20 Configuring Safety Integrated functions
SIMOTION D4x5-2
296 Commissioning and Hardware Installation Manual, 02/2012
Use of two PROFINET interfaces
An F-CPU can only be connected to one of the two PROFINET interfaces, because fail-safe
I/O transfer areas can only be configured either on the I device on the onboard PROFINET
interface or on the CBE30-2.
The PROFIsafe message frames are routed to the following drives:
Drives on the SINAMICS Integrated and CX32-2
Drives on the onboard PROFINET interface (X150 interface)
Drives on the CBE30-2 (X1400 interface)
The maximum quantity structure for PROFIsafe on PROFINET is therefore not increased by
using a second PROFINET interface.
Safety Integrated functions with TM54F
Safety Integrated functions are activated via fail-safe digital inputs on the TM54F. This
means that every drive control (SINAMICS Integrated of SIMOTION D4x5-2, CX32-2,
CU320-2, etc.) requires its own TM54F (assuming appropriate safety functions are to be
used on the respective Control Unit). Only one TM54F can be connected for each
SIMOTION D4x5-2, CX32-2 or SINAMICS S120 Control Unit.
Safety Integrated functions with PROFIsafe (PROFIBUS example)
Safety Integrated functions are activated via "PROFIsafe on PROFIBUS" safe
communication. Control (F logic) is based on a SIMATIC F-CPU connected via PROFIBUS
with PROFIsafe, e.g. a SIMATIC S7-300 F-CPU (see figure) or an ET 200S IM151-7 F-CPU
with PROFIBUS DP master interface module (not shown in the figure).
Figure 6-64 SIMOTION D, control of F functions via PROFIBUS with PROFIsafe
An example function can be found in:
(http://support.automation.siemens.
com/WW/view/en/36489289)

Table of Contents

Other manuals for Siemens SIMOTION D445-2

Related product manuals