Commissioning (software)
6.21 Quantity structures
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
299
As well as the maximum number of available performance points, the maximum quantity
structure of a functionality must also be taken into account (e.g. max. 6 servo drives with
125 µs current controller cycle clock).
Note
The following method just serves as a rough estimation of the possible quantity structures. It
is not a substitute for dimensioning with the SIZER configuration tool.
Higher utilization can result through the use of SINAMICS function modules (e.g. extended
messages/monitoring functions).
Table 6- 18 Estimation of the possible quantity structure
Information on dimensioning Your dimensioning (example)
Functionality Characteristic
2)
Max. number
3)
Performance points Number SUM of the
performance points
ALM/SLM with
DRIVE-CLiQ
1 1,3 1 1,3 Line module
5)
BLM 1 0,4
125 μs 6 2 For each
drive
6 12 Servo
1)
250 μs 6 1,2 For each
drive
2nd encoder Not relevant 6 2 encoder/
drive
0,1
250 μs 3 4 For each
drive
Vector
1)
500 μs 6 2 For each
drive
V
/
f
500 μs 12 1 For each
drive
Safety extended
function
12 ms Depending on
the drive
0,25 For each
drive
6 1,5
TB30 Not relevant 1 0,1
TM15 DI/DO 250 μs
1 ms
4 ms
8 0,5
0,2
0,1
For each
TM
TM31 250 μs
1 ms
4 ms
8 0,5
0,25
0,2
For each
TM
TM41 125 μs / 2 ms
4)
125 μs / 4 ms
4)
250 μs / 4 ms
4)
8 1
1
0,5
For each
TM
TM54F --- 1 0,5 For each
TM
TM15/TM17 Not relevant 8 1 For each
TM