Diagnostics
8.1 Diagnostics via LED displays
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
351
Meaning LED display
RDY RUN STOP SU/PF SF DP DP/MPI PN SY/MT OPT
Backing up diagnostic data and non-volatile data
Backing up diagnostic data and
non-volatile data (backup running)
x x Λ
(yellow)
Λ
(yellow)
x x x x x x
Backing up diagnostic data and
non-volatile data (backup
completed)
x Λ
(green)
x x x x x x x x
PROFINET IO interface for D4x5-2 DP/PN (onboard interface, X150)
Onboard PROFINET interface is
operating without error
; the data exchange to all
configured I/O devices is running
x x x x x x x 0 x x
Bus error x x x x x x x 1 (red) x x
Failure of a connected IO device x x x x x x x 2/1
(red)
x x
The PROFINET interface has not
yet synchronized with the send
cycle clock of PROFINET IO with
IRT, or
PROFINET IO with IRT has not
been configured
x x x x x x x x 0 x
The PROFINET interface has
synchronized to the send cycle
clock of PROFINET IO with IRT
x x x x x x x x 1
(green)
x
The PROFINET interface has
synchronized to the send cycle
clock of PROFINET IO with IRT.
(SINAMICS Integrated and ext. DP
interfaces have not synchronized
yet)
x x x x x x x x 2/1
(green)
x