Functions
5.2 Inverter control
Frequency inverter
92 Operating Instructions, 08.10. 2008, t.b.d.
Table 5- 11 Parameterizing the function
Parameter Description
P0700 = 3 Controls the motor using the digital inputs of the frequency inverter
P0727 = 3 Three-wire control, method 2
P0701 = 2 The enable signal to power-up the motor is issued with digital input 0
Further options:
The enable signal can be issued with any other digital input, e.g. with digital input 3
via P0704 = 2
P0702 = 1 The motor is started with digital input 1
Further options:
The motor can be started with any other digital input, e.g. with digital input 3 via
P0704 = 1
P0703 = 12 The direction of the motor is reversed with digital input 2
Further options:
The direction of the motor can be reversed with any other digital input, e.g. with
digital input 3 via P0704 = 12