Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
278 Function Manual, 05/2010, A5E03264275A
Example Trace SS2
'HVHOHFW66
'ULYHBU>@6,0RWLRQGLDJQRVWLFVVSHHGDFWXDOORDGVLGHVSHHGYDOXHRQ&RQWURO8QLW
'ULYHBU>@6,0RWLRQGLDJQRVWLFVVSHHGFXUUHQW6%5VSHHGOLPLWRQ&RQWURO8QLW
%LWWUDFNV
626DFWLYH
66DFWLYH
Figure 10-2 Example Trace SS2
Trace evaluation:
SS2 function is selected (time axis 0 ms; see bit "deselection SS2")
Response bit "SS2 active" is set (time axis approx 20 ms)
The drive decelerates along the configured OFF3 ramp (p1135)
Recording of r9714[0] (orange curve) shows whether the OFF3 ramp is active
SOS is activated (time axis approx. 500 ms; see bit "SOS active"); at this point the SS2
timer (p9552/p9352) has expired
Brown curve: Envelope curve of function SBR (r9714[1]); a fault is generated if this is
exceeded by the actual speed (r9714[0])
Note
Minor time differences (of the order of 2 to 3 safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.