SINAMICS PM230 (IP20) Power Module
Getting Started Guide
Fitting CU to PM
Mains and Motor terminals FSA ... FSC Screening methods
Access to motor and mains terminals FSD ... FSF
Motor and mains terminals FSD ... FSF
Maximum cable lengths
Components for United States / Canadian installations (UL/cUL)
Star and Delta connection
Using Maximum cable
length
EMI Level
Screened cables, filtered units (class A) 25 m Second Environment, C2*
Screened cables, filtered units (class A) 50 m Second Environment, C3*
Screened cables, unfiltered units, 50 m EMI Standard not fullfilled
Unscreened cables, filtered or unfiltered units 100 m EMI Standard not fullfilled
Inside the terminal box of Siemens motors
is a diagram showing both methods of
connections:
● Star connection (Y)
● Delta connection (∆)
The motor rating plate provides information
for each method of connection.
The Power Modules are fitted
with two-part-connectors. The
removable part of the connector
can be unplugged from the
Power Module by pressing the
release catch. The connectors
are not interchangeable.
Tightening torques:
● FSD 6 Nm (53 lbf.in)
● FSE 6 Nm (53 lbf.in)
● FSF 13 Nm (115 lbf.in)
2
1
6
9
2
3
3
10
5
8
8
1
2
5
1
7
8
4 4
① Line connection ⑦ Steel band
② Motor connection ⑧ Cable strap
③ Unshielded cable for line connection ⑨ Metal back plate
④ Shielded cable for motor connection ⑩ Shielding plate
⑤ Cable screen
⑥ Suitable clip to fix motor cable screen securely to metal back plate
Standards
European Low Voltage Directive
Europäische Niederspannungsrichtlinie
Directive européene basse tension
Directiva europea “Baja tension”
Direttiva europea sulla bassa tensione
ISO 9001
Siemens plc operates a quality management
system, which complies with the requirements
of ISO 9001
Siemens plc
Industry Sector
Drives Technology
Motion Control Systems
Varey Road
Congleton, CW12 1PH
United Kingdom
© Siemens AG, 2011
Subject to change without prior notice
Printed in the United Kingdom
Issue: 06/2011
*Only if EMC compliant connections are used.
Typical rating label
E060 5/0496 38 2 0 2 0 01
660-725
44 0-48 0
38 0-420
1LE1 002-1DB4 3-4A A0
kW
15
A
Hz
V
69 0
40 0
Y
60
50
50
17,1
29, 5
D-91056 Erlangen
3~ Mot.
1/min
cos φ
eta
89,4%
89,4%
0,8 2
0,8 2
0,8 2
17,3 1760
146 0
A
V
30,0 -3 0, 2
IEC / EN 60 034
160L IMB3
IP55
73 kg
29, 5
15
89,4%
146 0
Bea ri ng
DE
NE
6209 -2 ZC 3
6209 -2 ZC 3
46 0
17,4-17,5
30,2-29 ,8
Th.Cl. 155 ( F)
Tightening torques:
● FSA 0.4 Nm ... 0.5 Nm (3.5 ... 4.4 lbf.in)
● FSB 0.55 Nm ... 0.6 Nm (4.7 ... 5.3 lbf.in)
● FSC 1.2 Nm ... 1.5 Nm (10.6 ... 13.3 lbf.in)
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
In order that the system is UL/cUL-compliant, use UL/cUL-certified J-type fuses, overload circuit-breakers or intrinsically
safe motor protection devices. Use class 1 75° C copper wire only. Install the inverter with any external recommended
suppressor with the following features:
● Surge-protective devices; device shall be a Listed Surge-protective device (Category code VZCA and VZCA7)
● Rated nominal voltage 480/277 VAC, 50/60 Hz, 3-phase
● Clamping voltage VPR = 2000 V, IN = 3 kA min, MCOV = 550 VAC, SCCR = 65 kA
● Suitable for Type 1 or Type 2 SPD application
● Clamping shall be provided between phases and also between phase and ground.
Feature Specification