SWING radio fire detection system
10
008164_y_en_-- 111 | 152
FDCW241 FDOOT271
Communication protocol
(detector line)
FDnet –
Electromagnetic
compatibility
100 kHz…2.5 GHz: 30 V/m 100 kHz…2.5 GHz: 30 V/m
Permissible wind speed – Max. 5 m/s
Compatible conductor
cross-sections at the
connection terminals
0.2…1.5 mm
2
–
Battery service life >6 years >3 years
MC link interface 3.5 mm jack socket –
Operating temperature -10…+55 °C -10…+55 °C
Storage temperature -30…+75°C -30…+75°C
Air humidity (no moisture
condensation)
≤95 % rel. ≤95 % rel.
Protection category
(IEC 60529)
● IP40
● IP65 with housing FDCH221
IP44
Color ∼RAL 9010 pure white ∼RAL 9010 pure white
Dimensions 89 x 167 x 28 Ø 117 x 64 with FDB271
Standards
1
EN 54-17, EN 54-18,
EN 54-25
EN 54-5, EN 54-7,
EN 54-25
Approvals VdS: G212103 VdS: G212104
FDM273 FDM275 FDM275(F)
Electromagnetic
compatibility
● 10 kHz…100 kHz:
160 V/m
● 100 kHz…2.5 GHz:
30 V/m
● 10 kHz…100 kHz:
160 V/m
● 100 kHz…2.5 GHz:
30 V/m
● 10 kHz…100 kHz:
160 V/m
● 100 kHz…2.5 GHz:
30 V/m
Battery service life >3 years >3 years >3 years
Operating temperature -10…+55 °C -10…+55 °C -10…+55 °C
Storage temperature -30…+75°C -30…+75°C -30…+75°C
Air humidity (no moisture
condensation)
≤95 % rel. ≤95 % rel. ≤95 % rel.
Protection category
(IEC 60529)
IP44 IP24D IP24D
Color ∼RAL 3000 flame red ∼RAL 3000 flame red ∼RAL 3000 flame red
Dimensions 135 x 135 x 58 87 x 87 x 63 87 x 87 x 63
Standards
1
EN 54-11
(type B indoors)
EN 54-25
EN 54-11 (type A indoors)
EN 54-25
EN 54-11 (type A indoors)
EN 54-25
Approvals VdS: G213092 VdS: G216092 VdS: G216092
1
You will find more information about standards in the information about CE marking below