Test units and accessories
Detector tester RE8STCO
Testifire 1001
-
101 ST test kit
11
008164_y_en_-- 143 | 152
11.8 Detector tester RE8STCO – Testifire 1001-101 ST
test kit
Figure 5:
The test kit RE8STCO consists of
1x Testifire 2001-101 tester
1x RE8-S smoke capsule
1x RE8-CO CO capsule
2x rechargeable batteries
1x charger with 12 V connection cable
2x mains cables AC 110/120-220/240 V
1x USB cable.
The detector tester contains a smoke capsule or CO capsule. The detector tester is
positioned over the detector for the function check. The smoke or gas that is
emitted triggers an alarm.
In high rooms, detectors positioned at an angle can be reached and tested using
adapters and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered
separately.
The detector tester must not be used in electrical switching stat
ions or areas
where there is a danger of explosion.