Air sampling smoke detection
10
008164_y_en_-- 113 | 152
10.4.2 Type overview
Type Designation Order number Weight [kg]
FDBZ290 Air sampling smoke detection kit S54319-S32-A1 0.664
Accessories for air sampling smoke detection kit FDBZ290
Type Designation Order number Weight [kg]
DB110 Detector base (collective) S54319-F5-A1 0.052
DB721 Detector base with loop contact DB721 S54319-F11-A1 0.052
DB721D Detector base S54319-F15-A1 0.054
FDB202 Collective detector base, flat S54319-F3-F1 0.025
FDB222 Addressable detector base, flat S54319-F1-A1 0.026
FDBZ290-AA Air flow tube, length 600 mm S54319-B33-A1 0.340
FDBZ290-AB Air flow tube, length 1500 mm S54319-B33-A2 0.840
FDBZ290-AC Air flow tube, length 2800 mm S54319-B33-A3 1.570
FDBZ290-AD Mounting bracket S54319-B34-A1 0.402
FDOOT241-A9 Neural fire detector, ASA S54310-F11-A1 0.106
OOH740 Multi-sensor smoke detector, ASA S54320-F7-A3 0.124
PSR720-2 Parameter set resistor S54319-F17-A1 0.001
- Metal cable gland M20 x 1.5 A5Q00004478 0.036
- M20 x 1.5 metal counter nut A5Q00004479 0.006
10.4.3 Technical data
FDBZ290
Operating temperature -20...+50 °C
Air humidity ≤95 % rel.
Air flow tube Aluminum
Permissible air speeds 1…20 m/s
Air flow indicator ≥1 m/s
Housing of the air duct sampling chamber
● Material
● Protection category (IEC 60529)
● Color
ABS
IP54
~RAL 7001 silver grey
Smoke detector/detector base See 'Technology/design' section
System compatibility
● Sinteso
● Cerberus PRO
FDnet, collective
C-NET, collective
Approvals
● VdS G216035
Standards
EN 54-27 when used with specialized Sinteso or
Cerberus PRO smoke detectors