10.8.3 Technical data
DF1101-Ex
Operating voltage DC 16…28 V
Operating current (quiescent) 0.5 mA
Ext. alarm indicator (AI) 2
Connection factor KMK 6
Connection terminals 0.2…2.5 mm
2
Operating temperature -35…+70°C
Storage temperature -40…+75 °C
Air humidity
≤95 % rel. (no significant moisture condensation on the
viewing window)
Color ~RAL 9010 pure white
Protection category (IEC/EN 60529) IP67
Ex classification II 2 G Ex ib IIC T4 Gb (-35 °C ≤Ta ≤70 °C)
Standards
● For flame detectors
● For Ex areas
EN 54-10
IEC 60079-0, IEC 60079-11
Approvals
● VdS
● EC-type examination certificate
● LPCB
● DNV GL (marine)
G299085
PTB 02 ATEX 2161
LPCB 126bb/01
MEDB00003UN
Compatibility
● FDnet/C-NET
● Collective signal processing /
SynoLINE600, interactive, AnalogPLUS /
SynoLOOP
● With transponder FDCIO223 and safety barrier SB3