Automatic fire detectors
Multi
-
sensor fire detector FDOOT241
-
Ax, FDOOT241
-
8
2
14 | 152 008164_y_en_--
2.2.3 Technical data
FDOOT241-A3 FDOOT241-A4 FDOOT241-A5 FDOOT241-A9 FDOOT241-8
FDOOT241-A3,
FDOOT241-A4,
FDOOT241-A5,
FDOOT241-A9
FDOOT241-8
In the
AnalogPLUS
detector system
In the
SIGMALOOP
detector system
In the
Interactive
detector
system
In the collective
detector
system
In the MS8
detector system
In FDnet
Operating voltage
(modulated)
DC 16…28 V DC 10…28 V DC 21…33 V DC 14…28 V DC 14…28 V DC 12…33 V
Operating current
(quiescent)
190 μA 200 μA 200 μA 65…125 μA 200 μA 190…230 μA
External alarm indicators
(AI) which can be
connected
2 2 2 2 2 2
Communication protocol
AnalogPLUS SIGMALOOP Interactive Collective MS8/PMT FDnet
System compatibility
AlgoRex SIGMASYS AlgoRex AlgoRex,
SIGMASYS,
CZ10
SIGMASYS,
BMS,
SM80/88/D100,
SRS
FS20 ¹
Operating temperature
-25…+70°C -25…+70°C -25…+70°C -35…+70°C -25…+70°C -
Storage temperature
-30…+75°C -30…+75°C -30…+75°C -35…+75°C -30…+75°C -
Humidity
95 % rel.
Color
~RAL 9010 pure white
Protection category
(IEC 60529)
with detector base
FDB221, FDB222
IP43
Base attachment FDB291
IP43
Base adapter FDB281
IP44
Base adapter FDB241
and
detector base DB1131A,
or SPF3600
IP44
Base adapter FDB251
and
detector base DB1151A
IP44
Base adapter FDB299
and
collective detector base
DB1101A or SPF600
IP44
Standards
CEA 4021, EN 54-5, EN 54-7, EN 54-17, EN 54-27
2
Approvals
VdS
LPCB
DNV GL (marine)
G211125
126bh/02
-
G212007
-
-
G215057
126bh/07
-
G212036
126bh/03
MEDB000
03UK
G204133
-
-
-
-
-
Permissible wind speed
1…20 m/s
¹ FS20 compatibility in FDnet is assured subject to in-country FS20 software support.
2
EN 54-27 for FDOOT241-A3, FDOOT241-A4, FDOOT241-A9 only