Automatic fire detectors
Point detector FDOOT241
-
9, FD
OOT241
-
A, FDO241, FDT241
2
20 | 152 008164_y_en_--
2.3.3 Technical data
FDOOT241-9 FDOOT241-A FDO241 FDT241
Operating voltage (modulated)
DC 12…33 V
Operating current (quiescent)
65…230 μA 180…230 μA 130…200 μA
External alarm
indicators (EAI)
which can be
connected
Without sounder
base
2
With sounder
base
1
Communication protocol
FD20 or collective FDnet
System compatibility
FS20¹, AlgoRex, SIGMASYS
CZ10, CS11,
BC10, FC10,
XC10, FC330A,
FC700A, BMS,
SM80/88D100
Operating temperature
-25…+70°C -35…+70°C -25…+70°C -25…+50°C /
-25…+65 °C /
Depending on parameter settings
Storage temperature
-30…+75°C -35…+75°C -30…+75°C
Air humidity
95 % rel.
Color
~RAL 9010 pure white
Protection
category
(IEC 60529)
With detector base
FDB221/-AA,
FDB222, FDB291
IP43
Base FDB221 and
sealing element
FDBZ295
IP44
Base attachment
humid FDB293 or
base attachment
wet FDB295
Standards
CEA 4021, EN 54-5 EN 54-5
EN 54-17
EN 54-7
EN 54-27
Approvals:
VdS
LPCB
FM
DNV GL (marine)
G204007
126bh/01
3029351
G215052
G204017
126bf/02
3029351
MEDB00003UK
G204019
126bj/02
3046115
MEDB00003UR
Permissible wind speed
1…20 m/s
¹
FS20 compatibility in FDnet is assured subject to in-country FS20 software
support.