Manual call point
Manual call point FDM221/223/224
5
008164_y_en_-- 41 | 152
Manual call point FDM223
Indirect alarm activation by pushing in the glass insert and pressing the alarm
button
Open the door of the detector with the key to replace the glass insert. Reset the
alarm button before closing the door.
Protective cover DMZ1197-AC (accessory) protects the manual call point
against the glass being broken and the alarm activated accidentally.
Seal DMZ1197-AD (accessories) protects the manual call point in wet areas.
Fields of application:
For the immediate manual activation of an alarm
For indoor and outdoor application, also suitable for humid, wet, and dusty
environments
For surface-mounted and recess-mounted cable entries in easily
accessible locations
Manual call point FDM224
Direct alarm activation by pushing in the glass insert
Open the door of the detector with the key to replace the glass insert. The
alarm button is reset when the door is closed.
Fields of application:
For the immediate manual activation of an alarm
For indoor and outdoor application, also suitable for humid, wet, and dusty
environments
For surface-mounted and recess-mounted cable entries in easily
accessible locations
1 Metal cable gland (accessories) 2 Cable gripper
DMZ1197-AC
DMZ1197-AD