Manual call point FDM225/226 (direct alarm activation)
5
48 | 152 008164_y_en_--
FDM225-xx FDM225-xx with back box FDMH295-x FDM226-xx
● If you use back box FDMH295-R with the FDM225-xx, a hole with Ø ≤20 mm
must be drilled in the back box for the surface-mounted cable entry. Use metal
cable gland M20 x 1.5 with metal counter nut M20 x 1.5 (accessories).
● The manual call point FDM226-xx has two break-out openings on the top and
two on the bottom of the housing for cable entry purposes.
● If protection category IP66 is to be achieved with the FDM226-xx, the lateral
fastening tabs must be used to mount the back box. Cable entry must be
effected using metal cable gland M20 x 1.5 and metal counter nut M20 x 1.5
(accessories).
FDMH295-R