Manual call point FDM225/226 (direct alarm activation)
5
008164_y_en_-- 51 | 152
5.3.3 Technical data
FDnet operating voltage DC 12…33 V
Operating current (quiescent) 180 µA
Operating temperature -25…+70°C
Storage temperature -30…+75°C
Air humidity ≤95 % rel.
Communication protocol FDnet
Connection terminals 0.28…1.5 mm
2
Color ~RAL 3000, flame red
Design according to EN 54-11 Direct activation 'type A'
Environmental category according
to EN 54-11:
● FDM225-xx: In buildings
● FDM226-xx: In buildings and outdoor areas
Color ~RAL 3000, flame red
Protection category (IEC 60529): ● FDM225-xx: IP44
● FDM226-xx: IP66
Approvals: FDM225-RP
FDM225-RP (F)
FDM225-RG
FDM225-RG (F)
FDM226-RP FDM226-RG
● VdS G207092 G207092 G209194 G209194
● LPCB 126ap/01
126ap/10
126ap/02
126ap/11
126ap/03 126ap/04
● DNV GL (marine) - - MEDB00003UM -
System compatibility: ● FDnet: FS20, AlgoRex, SIGMASYS
● C-NET: FS720