231 (direct alarm activation)
5
008164_y_en_-- 53 | 152
5.4.3 Technical data
FDM231-RP FDM231-RP(F)
Operating voltage DC 12…33 V
Operating current (quiescent) Max. 180 µA
Ext. alarm indicator (AI) 1
Connection terminals 0.28…1.5 mm
2
Operating temperature -25…+65 °C
Storage temperature -30…+65 °C
Air humidity, non-condensing ≤95 % rel.
Communication protocol FDnet
Color ~RAL 3000 flame red
Protection category (EN 60529 /
IEC 529)
IP44
Standards EN 54-11, EN 54-17
Design Type A (direct activation)
Approvals
● VdS
● LPCB
G215064
531k/12
G215064
531k/13
System compatibility
● FDnet
● C-NET
FS20