Manual call point FDM243H 'Heavy Duty' (indirect alarm activation)
5
008164_y_en_-- 57 | 152
5.6.3 Technical data
FDM243H
Operating voltage DC 12…33 V
Operating current (quiescent) Max. 200 µA
Ext. alarm indicator (AI) 2
Connection terminals 0.2…2.5 mm
2
Operating temperature -35…+70 °C
Storage temperature -40…+70 °C
Air humidity, non-condensing ≤95 % rel.
Communication protocol FDnet
Color ~RAL 3000 flame red
Protection category (EN 60529 /
IEC 60529)
IP66
Standards EN 54-11, EN 54-17
Design according to EN 54-11 Type B (indirect activation)
Approvals
– VdS G214018
System compatibility
– FDnet
– C-NET
FS20
FS720