Alarm devices in the FDnet
7
66 | 152 008164_y_en_--
Base attachment humid FDB293
● For achieving a higher protection category
● For mounting in wet or humid environments
● Required when using detector heating unit FDBH291
● Required when using protective cage DBZ1194 or EMC-protective cage
FDBZ294
● Mounted between detector base and ceiling
● Detector base mounted quickly: The detector base simply clicks into place in
base attachment humid FDB293.
Base attachment wet FDB295
● Base attachment wet with additional integrated rubber seal for mounting in wet
or humid environments
● For achieving a higher protection category
● For mounting in wet or humid environments
● Required when using detector heating unit FDBH291
● Required when using protective cage DBZ1194
● Mounted between detector base and ceiling
● Detector base mounted quickly: The detector base simply clicks into place in
base attachment wet FDB295.
Designation plate DBZ1193A
● For labeling with the location address
● Can only be used with base attachment wet FDB295
Protective cage DBZ1194
● To protect the point detector from damage
● Can only be mounted in combination with the base attachment humid FDB293
or base attachment wet FDB295
DBZ1190-AA micro terminal and DBZ1190-AB connection terminal
● Micro terminal DBZ1190-AA
– Cable cross section up to max. 0.5 mm²
● Connection terminal DBZ1190-AB
– Cable cross section up to max. 2.5 mm²
– For connecting two external alarm indicators or the cable shielding