Input/output modules
FDCI221, FDCIO221
9
84 | 152 008164_y_en_--
FDCIO221 input/output module
Input for potential-free detector contact
Monitoring the input line for open line and short-circuit with terminating resistors
The input for status or alarm messages can be configured using the fire control
panel.
Output which can be configured via jumper:
Not monitorable: Potential-free relay contact (AC 22 V, 2 A or DC 30 V,
2 A)
Monitorable: Relay contact (DC 30 V, 2 A)
Status indicator by means of LED
Fields of application:
To activate a potential-free normally open or normally closed contact in
order to report technical statuses (e.g., fan control) or to activate an alarm
(e.g., sprinkler alarm)
For decentralized activation of alarming devices, fans, air conditioning
systems, lift controls, etc.
1 Potential-free detector contact 3 Connections for the detector line
2 Connections for the input 4 Connections for the output
FDnet/C-NET
FDnet/C-NET
1
2
4
3