Special detectors
Linear smoke detector FDL241
-
9
10
008164_y_en_-- 99 | 152
Type Designation Order number Weight [kg]
DLR1193 Reflector for short distance (foil) BPZ:4787840001 0.025
FDLU291
Adjustment kit for linear smoke
detector
A5Q00004905 0.840
RE10
Detector tester for linear smoke
detectors
BPZ:3685190001 0.345
TF04 Alarm test filter (absorption 77 %) BPZ:4931090001 0.005
10.1.3 Technical data
Linear smoke detector FDL241-9
Operating voltage addressed / collective DC 12…33 V / DC 14…28 V
Operating current (quiet) addressed / collective 0.8 mA / 0.7 mA
Number of external alarm indicators that can
be connected
2
Detection distance 10…100 m
Operating temperature -25…+60 °C
Storage temperature -30…+75°C
Air humidity (no moisture condensation) 95 % rel.
Communication protocol FDnet or collective (with and without current limitation)
Conductor cross section 0.2…1.5 m
Color ~RAL 9010 pure white
Protection category (IEC 60529) IP65
Standards EN 54-12
1
, EN 54-17, EN 62471
(
1
with detection distance of 10…100 m)
Approvals
VdS
LPCB
FM
G204063
126bd/02
3029351
System compatibility
FDnet
C-NET
FS20, AlgoRex, SIGMASYS
FS720, FC360
Collective system compatibility
CZ10, BC10, FC10, XC10, CS11, FC700A, FC330A,
SIGMASYS, BMS, SM80/88/D100
Detector heating unit DLH1191A
Operating voltage DC 20…33 V
Operating current (quiescent) 30…50 mA
Resistance 600 Ω