Loading...
$SSHQGL[6-
9
&*&
10 CHAph Characteristic of the O/C stage Ip
inverse [ ] Inverse
short in [ ] Short inverse
long inv [ ] Long inverse
mode inv [ ] Moderately inverse
very inv [ ] Very inverse
extr inv [ ] Extremely inverse
def inv [ ] Definite inverse
IsqaredT [ ] I-squared-t
never [ ] Never
10 D Delayfactor of inverse phase-current protec.
min. 0.5 s
max. 15.0 ©©©©
10 Ip Pick-up value inverse time O/C stage Ip
min. 0.1 I/In
max. 4.0 ©©©©
10 Ip dy Pick-up value inverse time O/C stage Ip (dyn)
min. 0.1 I/In
max. 4.0 ©©©©
10CALCph RMS format for inverse time O/C protection
noHARMON [ ] Without harmonics
HARMONIC [ ] With harmonics
10M.CLph Manual close
I>>undel [ ] I>> undelayed
I>undela [ ] I> undelayed
Ip undel [ ] Ip undelayed
INEFFECT [ ] Ineffective
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
11 O/C EARTH - O/C PROTECTION EARTH FAULTS
11 O/C e O/C protection for earth faults
ON []on
OFF [ ] off
11 IE>> Pick-up value of the high-set stage IE>>
min. 0.05 I/In
max. 25.00/Ñ ©©©©
11IE>>dy Pick-up value of high-set E/F stage IE>> (dyn)
min. 0.05 I/In
max. 25.00/Ñ ©©©©
11 TIE>> Trip time delay of the high-set stage IE>>
min. 0.00 s
max. 60.00 ©©©©
11 IE> Pick-up value of the overcurrent stage IE>
min. 0.05 I/In
max. 25.00/Ñ ©©©©
11 IE>dy Pick-up value of def. time E/F stage IE> (dyn)
min. 0.05 I/In
max. 25.00/Ñ ©©©©
11 TIE> Trip time delay of the overcurrent stage IE>
min. 0.00 s
max. 60.00 ©©©©
www . ElectricalPartManuals . com