$SSHQGL[6-
9

&*&
01 T-CL Maximum close command duration
min. 0.01 s
max. 60.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
10 O/C PHASE - O/C PROTECTION PHASE FAULTS
10 O/Cph O/C protection for phase faults
ON []on
OFF [ ] off
10 Tdyn Duration of temporary pick-up value c/o
min. 0.1 s
max. 10000.0 ©©©©
10 I>>> Pick-up value of the high-set inst. stage I>>>
min. 0.3 I/In
max. 12.5/Ñ ©©©©
10I>>>dy Pick-up val. of high-set ins. stage I>>> (dyn)
min. 0.3 I/In
max. 12.5/Ñ ©©©©
10 I>> Pick-up value of the high-set stage I>>
min. 0.1 I/In
max. 25.0/Ñ ©©©©
10 I>>dy Pick-up value of the high-set stage I>> (dyn)
min. 0.1 I/In
max. 25.0/Ñ ©©©©
10 TI>> Trip time delay of the high-set stage I>>
min. 0.00 s
max. 60.00 ©©©©
10 I> Pick-up value of the overcurrent stage I>
min. 0.1 I/In
max. 25.0/Ñ ©©©©
10 I>dy Pick-up value of the O/C stage I> (dyn)
min. 0.1 I/In
max. 25.0/Ñ ©©©©
10 TI> Trip time delay of the overcurrent stage I>
min. 0.00 s
max. 60.00 ©©©©
10 REPph Measurement repetition
NO []no
YES [ ] yes
10 CHAph Characteristic of the O/C stage Ip
inverse [ ] Normal inverse
short in [ ] Very inverse
extr.inv [ ] Extremely inverse
long inv [ ] long inverse
never [ ] Never
10 Tp Trip time delay inverse time O/C stage Ip
min. 0.05 s
max. 3.20 ©©©©