$SSHQGL[6-
9
&*&
Reference Table for Functional Parameters 7SJ600
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
PARAME. - PARAMETER SETTINGS
00 CONF. - SCOPE OF FUNCTIONS
00 O/Cch Characteristic of O/C protection
def TIME [ ] Definite time
I>>> I>> [ ] I>>> I>>
IEC inv. [ ] Inverse time
ANSI inv [ ] ANSI inv
IEC O/C [ ] IEC O/C
ANSI O/C [ ] ANSI O/C
nonEXIST [ ] Non-existent
00 O/Cdy temporary pick-up value change over (O/C-st.)
nonEXIST [ ] Non-existent
EXIST [ ] Existent
00 UNB.L Unbalanced load protection
nonEXIST [ ] Non-existent
EXIST [ ] Existent
00 O/L Thermal overload protection
nonEXIST [ ] Non-existent
pre LOAD [ ] With memory
no preLD [ ] Without memory
00 STRT Supervision of startup time
nonEXIST [ ] Non-existent
EXIST [ ] Existent
00 AR Internal auto-reclose function
nonEXIST [ ] Non-existent
EXIST [ ] Existent
00CIRsup Trip circuit supervision
nonEXIST [ ] Non-existent
with 2BI [ ] No resist., 2 BI
bypass-R [ ] bypass resistor,1 BI
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
01 POWER SYST.DAT - POWER SYSTEM DATA
01 FREQ Rated system frequency
50Hz []fN50Hz
60Hz []fN60Hz
01 CT2 Connection of CT2
IL2 [ ] IL2
IE []IE
01 InPRI Primary rated current
min. 10 A
max. 50000 ©©©©
01 InSEC Secondary rated current
1A []1A
5A []5A
01 T-TRP Minimum trip command duration
min. 0.01 s
max. 32.00 ©©©©