$SSHQGL[6-
9

&*&
¿©©©©§©©©©©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©§©©§©§©¤
FNo.Text Meaning OpFtIO
¨©©©©ª©©©©©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©ª©
1779FD L13 O/C fault detection L1-L3 C O
1780FD L13E O/C fault detection L1-L3-E C O
1781FD L23 O/C fault detection L2-L3 C O
1782FD L23E O/C fault detection L2-L3-E C O
1783FD L123 O/C fault detection L1-L2-L3 C O
1784FDL123E O/C fault detection L1-L2-L3-E C O
1785FD E O/C fault detection E only C O
1800FD I>> O/C fault detection stage I>> CG O
1805Trp I>> O/C protection I>> phase trip C O
1810FD I> O/C fault detection stage I> CG O
1815Trip I> O/C protection I> phase trip C O
1820FD Ip O/C fault detection Ip CG O
1825Trip Ip O/C protection Ip phase trip C O
1831FD IE>> O/C fault detection IE>> earth CG O
1833TrpIE>> O/C protection IE>> earth trip C O
1834FD IE> O/C fault detection IE> earth CG O
1836Trp IE> O/C protection IE> earth trip C O
1837FD IEp O/C fault detection IEp earth CG O
1839Trp IEp O/C protection IEp earth trip C O
1850FD dyn O/C prot. : dynamic Parameters activ CG O
2701>AR on >AR: Switch on auto-reclose function IO
2702>AR off >AR: Switch off auto-reclose functio n IO
2732>AR St. >AR: Start external CGCGIO
2733>ARblSt >AR: External Blocking of Start CGCGIO
2734>ARblCl >AR: External Blocking of reclosure CGCGIO
2736AR act. AR: Auto reclosure is active CG O
2781AR off AR: Auto-reclose is switched off CG O
2801AR i pg AR: Auto-reclose in progress CG O
2851AR ClCm AR: Close command from auto-reclose CG O
2863AR dTrp AR: Definitive trip CG O
2872AR Strt AR: Start CG O
2873AR blSt AR: blocked CG O
2874AR blCl AR: Reclosure blocked CG O
2875AR blMC AR: Blocked by manual close CG O
2876AR DT AR: Dead time C C O
4632>SWblo. >Switching authorization: blocked IO
4640Q0 Clo. Control-Close-Command CB-Q0 C O
4641Q0 Trp. Control-Trip-Command CB-Q0 C O
5143>I2 blk >Block unbalanced load protection IO
5144>revPhR >Reversed phase rotation CG IO
5151I2 off Unbalanced load prot. is switched off CG O
5152I2 blk Unbalanced load protection is blocked CG O
5153I2 act Unbalanced load protection is active CG O
5159FD I2>> Unbalanced load: Fault detec. I2>> CG O
5165FD I2> Fault detection neg. seq. I (I2>) CG O
5170Trp I2 neg. seq. I. (I2) prot.: Trip C O
6757TrpI>>> O/C protection I>>> phase trip CG O
6758>I>>>bk >inst. high set prot.: Block stage I>>>CG IO
6801>SRT bk >Starting time supervision: Block stage IO
6811SRT off Supervision of starting time off CG O
6812SRT blk Supervision of starting time blocked CG O
6813SRT act Supervision of starting time active CG O
6821SRT Trp Supervision of starting time trip CGC O
6851>SUP bk >Blocking trip circuit supervision IO
6852>TrpRel >Trip circuit supervision: Trip relay CG IO
6853>CBaux >Trip circuit supervision: CB aux. CG IO
6861SUP off Trip circuit supervision off CG O
6862SUP blk Trip circuit supervision blocked CG O
6863SUP act Trip circuit supervision active CG O
6864SUPnoBI TC superv. blocked: BI not marshalled CG O
6865CIR int Trip circuit interrupted CG O
¥©©©©¦©©©©©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©¦©¾