24 I2>> Pick-up value for high current stage
min. 8 %
max. 80 ©©©©
24 TI2>> Trip time delay for high current stage
min. 0.00 s
max. 60.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
27 THERM OVERLOAD - THERMAL OVERLOAD PROTECTION
27 O/L State of thermal overload protection
ON []on
OFF [ ] off
27 k-FAC K-factor for thermal overload protection
min. 0.40
max. 2.00 ©©©©
27 Ì-CON Time constant for thermal overload protection
min. 1.0 min
max. 999.9 ©©©©
27 f-Ìco Multiplier of time constant at standstill
min. 1.00
max. 10.00 ©©©©
27 Î-ALM Thermal warning stage
min. 50 %
max. 99 ©©©©
27 tL Time-setting for I-squared-t overload stage
min. 1.0 s
max. 120.0 ©©©©
27 IL Pick-up value for I-squared-t overload stage
min. 0.4 I/In
max. 4.0 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
28 START TIME SUP - STARTING-TIME SUPERVISION
28 STRT Supervision of starting time
ON []on
OFF [ ] off
28t strt permissible starting time
min. 1.0 s
max. 360.0 ©©©©
28I strt permissible starting current
min. 0.4 I/In
max. 20.0 ©©©©
28I> blk Block of the I>/Ip stages during start-up
NO []no
YES [ ] yes
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©