$SSHQGL[6-
9

&*&
34 AR - AUTO-RECLOSE FUNCTION
34 AR Auto-reclose function
ON []on
OFF [ ] off
34 ARcnt Number of shots
min. 1
max. 9 ©©©©
34 AR T1 Dead time for 1st shot
min. 0.05 s
max. 1800.00 ©©©©
34 AR T2 Dead time for 2nd shot
min. 0.05 s
max. 1800.00 ©©©©
34 AR T3 Dead time for 3rd shot
min. 0.05 s
max. 1800.00 ©©©©
34 AR T4 Dead time for 4th to 9th shot
min. 0.05 s
max. 1800.00 ©©©©
34 T-REC Reclaim time after successful AR
min. 0.05 s
max. 320.00 ©©©©
34 T-LOC Lock-out time after unsuccessful AR
min. 0.05 s
max. 320.00 ©©©©
34 T-BLM Blocking duration with manual close
min. 0.50 s
max. 320.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
38 DELAY ANNUNC. - ANNUNCIATION DELAY TIMES
38T-Anc1 Delay time for 1st user defined annunciation
min. 0.00 s
max. 10.00/Ñ ©©©©
38T-Anc2 Delay time for 2nd user defined annunciation
min. 0.00 s
max. 10.00/Ñ ©©©©
38T-Anc3 Delay time for 3rd user defined annunciation
min. 0.00 s
max. 10.00/Ñ ©©©©
38T-Anc4 Delay time for 4th user defined annunciation
min. 0.00 s
max. 10.00/Ñ ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
39CIRsup - TRIP CIRCUIT SUPERVISION
39CIRsup Trip circuit supervision
ON []on
OFF [ ] off