Siemens SMART 7KT - Modbus Register Addresses - Integer Parameters

Siemens SMART 7KT
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
SMART 7KT0310 Manual
Readable / writable parameters: [Data Structure: Integer]
Address
Hex
Address
Parameter Range
Length
(Register)
40000 0x00 Password Minvalue:0 Maxvalue:9998 1
40001 0x01 N/WSelection Value: 0 Meaning:3P4W 1
Value: 1 Meaning:3P3W 1
Value: 2 Meaning:1P2W-P1 1
Value: 3 Meaning:1P2W-P2 1
Value: 4 Meaning:1P2W-P3 1
40002 0x02 CTSecondary Minvalue:1 Maxvalue:5 1
40003 0x03 CTprimary(CTSecondary=5)(A) Minvalue:5 Maxvalue:10000 1
CTprimary(CTSecondary=1)(A) Minvalue:1 Maxvalue:10000
40004 0x04 PTSecondary Minvalue:100 Maxvalue:500 1
40006 0x06 PTprimary Minvalue:100 Maxvalue:500kV 2
40007 0x07 Slaveid Minvalue:1 Maxvalue:255 1
40008 0x08 Baud rate Value:0x0000 Meaning:300 1
Value:0x0001 Meaning:600
Value:0x0002 Meaning:1200
Value:0x0003 Meaning:2400
Value:0x0004 Meaning:4800
Value:0x0005 Meaning:9600
Value:0x0006 Meaning:19200
40009 0x09 Parity Value:0x0000 Meaning:None 1
Value:0x0001 Meaning:Odd
Value:0x0002 Meaning:Even
40010 0x0A Stop bit Value:0x0000 Meaning:1 1
Value:0x0001 Meaning:2 1
40011 0x0B BacklightOFF Min Value: 0 MaxValue:7200 1
40012 0x0C Factory Default Value: 1 Meaning:Settofactorysettingrange 1
40016 0x10 AutoModePages Min Value: 1 MaxValue:22
Page No Meaning
40017 0x11 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40018 0x12 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40019 0x13 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40020 0x14 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40021 0x15 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40022 0x16 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40023 0x17 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40024 0x18 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40025 0x19 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40026 0x1A PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40027 0x1B PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40028 0x1C PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40029 0x1D PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40030 0x1E PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40031 0x1F PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40032 0x20 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40033 0x21 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40054 0x36 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40055 0x37 PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40059 0x3B PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40060 0x3C PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40061 0x3D PageAddressSequence 1-22 1-FirstPage;22-LastPage 1
40034 0x22 DemandIntervalMethod Value:0x0000 Meaning:Sliding 1
Value:0x0001 Meaning:Fixed 1
40035 0x23 DemandIntervalDuration MINValue:1 MAX Value: 30 1
40036 0x24 DemandIntervalLength MINValue:1 MAX Value: 30 1
40043 0x2B ResetMax Value: 1 Meaning:ResetallMaxpower 1
40044 0x2C ResetEnergy Value: 1 Meaning:Resetallenergytofactorysettingrange 1
40046 0x2E ResetONHour Value: 1 Meaning:ResetONhour 1
Modbus register addresses list (Continued)