EasyManua.ls Logo

Siemens SMART 7KT - Certifications and Standards Compliance

Siemens SMART 7KT
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
SMART 7KT0310 Manual
Measured variables
Measured variable On display On communication
VoltageV
L-N
,V
L-L
● ●
Current
● ●
Neutralcurrent
● ●
Frequency
● ●
Powerfactor
● ●
Activepower
● ●
Reactivepower
● ●
Apparentpower
● ●
Activeenergy(Import,Export,Total)
● ●
Reactiveenergy(Import,Export,Total)
● ●
Apparentenergy
● ●
Maxdemand(current)oversetdemandperiod
● ●
Maxdemand(active,reactiveandapparentpower)oversetdemand
period
● ●
Phaseangleof3phases
● –
THD%(Current)
● ●
THD%(Voltage)
● ●
Individualharmonics(Current)
– ●
Individualharmonics(Voltage)
– ●
–:Notthere
●:Available
Measuring accuracy
Measured variable Error limits
VoltageV
L-N
0.5%ofFullscale(300VAC)
VoltageV
L-L
Fullscale0.5%
Current PhaseCurrent:0.5%offullscale
Neutralcurrent:1%offullscale
Frequency 0.1%
ForL-NVoltage>20V,
ForL-LVoltage>35V
Powerfactor 0.01Digit
Activepower 1%
Reactivepower 1%
Apparentpower 1%
Activeenergy Class1(asperIEC62053-21)
Reactiveenergy Class2(asperIEC62053-23)
Apparentenergy 1%
Phaseangleof3phases 1%
THD(Current) 1%
THD(Voltage) 1%
Harmonics(Current) 1%
Harmonics(Voltage) 1%
Whenmeasuringonexternalcurrenttransformersorvoltage
transformers,theaccuracyofthemeasurementdependsonthe
qualityofthetransformer.
IEC Standards
Description Standard
Energyaccuracy IEC62053-21|Activeenergy
EMCrequirements IEC61326-1:2012
Degreeofprotectiontest(IP) IEC60529
Safetyrequirements IEC61010-1:2010and
IEC61010-2-030:2010
Vibrationandmechanicalshock IEC62052-11
Certications
SMART7KTmultifunctionmeterconformstoIEC
standards,IPCelectronicsassemblystandardand
RoHS