SXL-EX
7906
s Industry, Inc.
Building Technologies Division
s
DataSheet
FireSafety &Security Products
SXL-EX Fire Control Panel
Conventional Zone Fire Alarm Control Panel
System Overview
Model SXL-EX from Siemens ─ Fire Safety is a
microprocessor-based fire-alarm control panel (FACP)
supplied with four (4) conventional zones, and is
expandable to eight (8) conventional zones. Model
SXL-EX also contains features, such as: field
programmability; power-limited circuits, one-person
person test; remote annunciation, and sufficient
power to meet ADA requirements for signaling.
Model SXL-EX is designed to meet the varied fire-
alarm needs for small office buildings, apartment
buildings, department stores, hotels, strip malls or
anywhere a cost-efficient, general-purpose FACP is
required.
Additionally, the SXL-EX can be used to supply remote
bell power for larger systems such as the MXL FACP.
Initiating Circuits
Model SXL-EX has four (4) conventional, Style B (Class
B) zones, which are typically compatible with the
ionization detector (Model DI-3*); the photoelectric
detector (Model PE-11*) and the photo-thermal
detector (Model PE-11T*); Siemens Fire Safety thermal,
flame and beam detectors, and the MS Series of
manual stations. (Please refer to the detector-
compatibility list in the wiring diagram for specific
compatibility questions).
• Four (4) zones ─ expandable to eight (8) zones
• Series 3 and 11 compatible detectors and
accessories
• Microprocessor-based control
• Factory programmed
─ field configurable
• Two (2) Style Y notification appliance circuits
(NACs)
• 3 Amps notification and auxiliary power
• 24 and 60-hour battery backup
• Eight (8) ‘Form C’ relay-output option
• 220/240 VAC, 50 Hz power-supply option
• Remote serial-annunciator option
• Sprinkler supervisory service
• Non-silenceable bell service
• Alarm verification by zone
• One-person test feature
• Zone / output bypass feature
• Subsequent Alarm and Trouble commands with
24-hour reminders
• Alarm, Trouble and Supervisory last-event records
• UL 864 9
th
Edition Listed & ULC Listed;
CSFM Approved
* AsterisksshowninthesecondcolumndenoteModelsDI‐3C;
P
‐11CandP
‐11TC,res
ectivel
,inCanada
ARCHITECT AND ENGINEER SPECIFICATIONS