TX-I/O Modules
24
Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference
588-587 CONFIDENTIAL: For internal use only 4/6/2010
TX-I/O LCD Display by Point Type.
Point Type
(Displays in LCD Bottom Row)
Normal Operation
(Displays in LCD Top Row)
Digital Input, N/C Contact
Inactive
Active
Digital Input, N/O Contact
Inactive
Active
Super Universal I/O Modules (TXM1.8X and TXM1.8X-ML)
The TXM1.8X and TXM1.8X-ML Super Universal I/O modules provide 8 points, which
can be individually configured as analog output, analog input, or digital input to best
meet the specific application needs.
TXIO0024R1
TXM1.8X
2
3 7 1511
19 21 23 25 27 29 31 33
(5) (7)(6) (8)
(1) (2) (3) (4) (5) (6) (7) (8)
4
(1)
6 8
(2)
10 12
(3)
14
20 24 28 32
16
(6)
(4)
VVVV
VVVV
TXIO0025R1
TXM1.8X-ML
2
3
VVVV
VVVV
71511
19 21 23 25 27 29 31 33
(5) (6) (7) (8)
(1) (2) (3) (4) (5) (6) (7) (8)
4
(1)
68
(2)
10 12
(3)
14
20 24 28 32
16
(4)
+
NOTE:
All supply terminals are connected in the I/O module, not in the terminal base.
All Super Universal I/O modules provide:
AC supply voltage for peripheral devices such as valves and actuators
Green LED status per I/O point that varies in intensity according to the voltage and
current (directly proportional)

Questions and Answers: