43/54 
Siemens  TX-I/O™ Module system – Functions and operation  CM110561en_08 
Building Technologies  Digital output functions  2018-10-25 
•  If the difference between the stroke model and the process value (∆Y) is more than 
half the deadband plus the hysteresis, this generates an OPEN or CLOSE pulse 
which is long enough to return the actuator to a position within the deadband. 
•  The minimum pulse length is equal to the runtime multiplied by the hysteresis. 
 
 
 
Start synchronization, if selected, is automatically initiated after reset. 
The synchronization is not interrupted by any other event. 
•  NONE      No synchronization 
•  SINGLEOPEN    OPEN command during 1.5 x runtime OPEN  
•  SINGLECLOSE    CLOSE- command during 1.5 x runtime CLOSE 
 
Synchronization when stroke model reaches the end position (0% or 100%): 
•  Normal operation: 
 
Permanent synchronization (0% and 100%) 
Permanent synchronization (100%) 
Permanent synchronization (0%) 
1.5 * Rise Time (100%) or 1.5 * Fall Time (0%) 
1.5 * Rise Time (100%) or 1.5 * Fall Time (0%)  
every 10 minutes 
1.5 * Rise Time (100%) every 10 minutes 
1.5 * Fall Time (0%) every 10 minutes 
1.5 * Rise Time (100%) or 1.5 * Fall Time (0%)  
every 20 minutes 
1.5 * Rise Time (100%) every 20 minutes 
1.5 * Fall Time (0%) every 20 minutes 
 
•  Local override:     
OPEN or CLOSE relay is active as long as button is pressed, synchronization is 
disabled. 
 
•  Tool override, Remote Override: in the end positions, CONTINOPEN / 
CONTINCLOSE applies, i.e. OPEN or CLOSE relay goes to maintained contact. 
If this behavior is not desired, command the actuator to 0.1% / 99.9% instead of 0% / 
100%. 
For commissioning purposes, a synchronization can be forced: 
•  NONE      No synchronization 
•  CONTINOPEN    Continuous OPEN command 
•  SINGLEOPEN    OPEN command during 1.5 x runtime OPEN  
(series D and higher) 
•  CONTINCLOSE    Continuous CLOSE command  
•  SINGLECLOSE    CLOSE- command during 1.5 x runtime CLOSE  
(series D and higher)