WL Circuit Breaker
1/29
WL Selection and Application Guide • 2005
Technical Data
WL Non-Automatic Switches UL 489
Ratings
Frame Size I Frame Size II Frame Size III
Rating Nominal Current 800 1200 1600 2000 2500 3000 4000 5000
Rating Class H
HL LLLLL
Short-time Withstand
Current
(kA RMS) 50/60 Hz 0.5 s 65 65 85 85 85 85 85 85
Breaking Capacity with
External Relay (kA RMS)
50/60 Hz,
instantaneous trip
240V 85 85 100 100 100 100 100 100
480V 85 85 100 100 100 100 100 100
600V 65 65 85 85 85 85 85 85